PLEASE BE CONFIDENT THIS MODEL IS NOT AT ALL SAME AS SPD SOLD ON ONLINE ECOMMERCE WEBSITE , PRODUCT HAS BEEN INSTALLED & TESTED IN PALAMU (JHARKHAND) , & SOME MINES OF ODISHA INDIA'S MOST LIGHTENING PRONE AREA,
product is 1 GBPS capable 100 mbps SPD are much lower priced
WORKING ON -25 DEGREES AROUND SOME MILITARY AREAS WITHIN HIMALAYAS
WORKING ON 97% HUMIDITY IN AREA LIKE BHUBANESHWAR,PATNA,KOLKATA, SOME PARTS OF EGHALAYAS & REMOTE SENSORS LOCATED AROUND SUNDERBAN DELTA
18 MONTH WARANTY
useful for:
- OUTDOOR CCTV
- NETWORK CCTV
- NETWORK SWITCHES
- SFP FIBER SWITCHES
- CPE
- SM
- OUTDOOR WIFI ACCESS POINTS
- OUTDOOR 4G/5G ROUTERS IoT &
- OUTDOOR SENSOR , ACTUATORS, TRANSDUCERS WITH RJ 45 PORTS
) Product Parameters
|
Parameter |
Power |
Network signal |
|
Protection Class |
Power |
Network signal |
|
Operating Voltage (Un) |
48V |
5V |
|
Rated Current |
850mA |
— |
|
Transmission rate (bps) |
— |
100M/1000M |
|
Impulse Voltage (10/700 μs) |
C–X: 6KV; X–X (Data): 2KV; X–X (Power): 2KV |
|
|
Voltage Protection Level (Up) |
C–X = 80V; X–X (Data) = 8V; X–X (Power) ≤ 70V |
|
|
Transmission rate Vs |
1000Mbps |
|
|
Insertion Loss |
— |
≤ 0.2dB |
|
Response Time |
≤ 1ns |
≤ 1ns |
|
Protected Core |
1/2、3/6 & 4/5、7/8 |
1–8 line |
|
Interface Model |
RJ45 |
|
|
Working Environment |
Temperature: −40°C to +70°C; Relative humidity < 90% |
|
|
Dimension (L × W × H) |
102 × 66 × 28mm |
3) Product Installation
1. This product is installed between signal channel and protected equipment. The output end is connected with protection equipment.
2. All wirings must be solid and be connected by electric.
3. The earth terminal of SPD should be connected to earth ground. Ground screw with terminal forks which is applied to connect grounding collection row and earth terminal of SPD. After connecting the ground wire well, be sure to tighten the screws. The grounding line: BVR ≥ 2.5mm². The length of the ground wire to grounding collection row should be less than 1m. Lightning-proof grounding should be consistent with lightning protection regulatory requirements. Grounding wire should be as thick and short as possible. Resistance should be less than 4Ω.
Network POE power supply SPD
1) Product Description
The product uses imported advanced circuit with high-quality design, this circuit design layout is reasonable and performance is stable, from the top to bottom, from the over flow to over-voltage all have made a comprehensive protection. Its internal structure is consists of a network data cable and AC power cord two kinds of surge protection solutions, which will ensure it can prevent your systems and equipment from surge damage because of electrostatic discharge or lightning.
◆ Its performance is excellent and flow capacity is large, which can effectively prevent equipment damage which caused by the power, network and other equipment, the potential difference between the transient increase.
◆ It has muti-level protection circuit, low residual voltage, and excellent protective effect. It has advantage of extremely quick respond, large intake capacit.
◆ It has an excellent and stable signal transmission performance and a long service.
◆ It is suitable for the compound lighting arrester SPD of network cable of Ethernet and Supply power.